BSTCALTEK

Product information

BT751 - Insulation Tester with Voltage Test

Be the first to review this product

US$0.00

Quick Overview

BT751 is a portable insulation meter designed for electrical installer to perform insulation resistance measurements with test voltage up to 1000VDC, 600V voltage measurements and continuity test of earth conductors, on civil and industrial electrical environments.


Download Specification: BT751.pdf

BT751 - Insulation Tester with Voltage Test

Double click on above image to view full picture

Zoom Out
Zoom In

More Views

Details

BT751 is a portable insulation meter designed for electrical installer to perform insulation resistance measurements with test voltage up to 1000VDC, 600V voltage measurements and continuity test of earth conductors, on civil and industrial electrical environments.

And other special features are LOCK function, adjustable timer and large LCD backlight display. The LOCK function can perform a continuous insulation measurement to the device under test. Adjustable timer from 2s to 60s permits users to decide the duration of the measurements. Its large LCD display with backlight function enable user to work in weak/dim light environment.

 

Features:

Ÿ- 4 Digits LCD display with maximum 9999 counts reading and symbol

Ÿ- Function keys: ZERO、TEST、LOCK。

Ÿ- Continuity Test

Ÿ- Insulation resistance

Ÿ  250V: 4M ~ 1000M Ohm

Ÿ  500V: 4M ~ 2000M Ohm

Ÿ  1000V: 4M ~ 4000M Ohm

Ÿ- DC voltage:0.1V~600V

Ÿ- AC voltage:0.1V~600V

Ÿ- Low battery indication

Ÿ- Auto power off

Ÿ- Auto discharge

Ÿ- Conforms to EN61557 and EN61010-1 CAT III 1000V/ CAT IV 600V safety standard

 


Technical Specification:

Accuracies are ± (% of reading + number of least significant digits), at 23 ±5℃, less than 70%RH 

 

AC voltage measurement

Range

Resolution  Accuracy  Input Impedance  Overload Protection 
0.1~600.0V 0.1V (0.8% rdg +4 dgt) 3MΩ 605 VAC max RMS

Crest Factor:√2

 

DC voltage measurement

Range 

Resolution 

Accuracy 

Input Impedance 

Overload Protection 

0.1~600.0V

0.1V

(0.5% rdg +1 dgt)

3MΩ

605 VAC max RMS

 

Continuity Test

Range 

Resolution 

Accuracy

Overload Protection

0.1 - 199.9 Ohm

0.1 Ohm

+/- (2.0% rdg + 3 dgt)

605V AC max RMS per 1 minute

Buzzer sound when resistance <30 OHM

 

LO Ohm : 200mA Continuity of protection conductors

Range

Resolution

Accuracy

Overload Protection

0.01 - 19.99 Ohm

0.01 Ohm

+/- (2.0% rdg + 3 dgt)

605V max RMS

Test current: >200mA DC up to 5OHM (measuring cables resistance included)

Test current: >45mA DC over 5OHM  (measuring cables resistance included)

Open circuit voltage: 4 < V0 < 24V

 


M Ohm : Insulation resistance (Auto Range)

Test Voltage Range(OHM) Resolution(OHM) Accuracy Overload Protection
250V 0.001 - 0.100M 0.001M +/- 10 dgt 605V max RMS
0.101 - 3.999M 0.001M +/- (2.0% rdg + 5 dgt)
4.00- 39.99M 0.01 M
40.0 - 399.9M 0.1 M +/- (5.0% rdg + 5 dgt)
400 -1000M 1M
500V 0.001 - 0.250M 0.001M +/-  15 dgt
0.251 - 3.999M 0.001M +/- (2.0% rdg + 5 dgt)
4.00- 39.99M 0.01 M
40.0 - 399.9M 0.1M
400- 2000M 1M +/- (5.0% rdg + 5 dgt)
1000V 0.001 - 0.250M 0.001M +/-  15 dgt
0.251 - 3.999M 0.001M +/- (2.0% rdg + 5 dgt)
4.00- 39.99M 0.01 M
40.0 - 399.9M 0.1M
400 - 1000M 1M +/- (3.0% rdg + 5 dgt)
1000 - 4000M 1M +/- (5.0% rdg + 10 dgt)

AutorangeOpen circuit voltage: <1.3 x V0

Accuracy of nominal voltage: –0% +10%

Short circuit current: <3.0mA

Nominal testing current: 1mA @ 1KW x V (1mA @ 500KΩ)

 

General Specification:

Display

:

4 digit LCD with max. reading 9999 counts + symbol and decimal point

Sampling rate

:

2 times per second

Memory

:

Data Hold

Operating Humidity

:

<70% RH

Operating Temperature

:

0°C to 40°C

Storage Humidity

:

<75% RH

Storage Temperature

:

-10°C to 60°C

Weight

:

Approx. 450g. (Including battery)

Battery Type

:

6 x standard 1.5 V – LR6 – AA – AM3 – MN 1500

Battery life

:

Typical 50hour (DMM mode); typical 1000 tests (Insulation)

Sleep mode

:

After 10 minutes (Approx.)

Dimension

:

74 (W) x 135 (H) x 30 (D) mm.

 

Product Tags

Use spaces to separate tags. Use single quotes (') for phrases.